Commercial Building Energy Audit Reveal Blog cover

What Does a Commercial Building Energy Audit Reveal That Your BAS Doesn’t?

A building automation system (BAS) shows what your equipment is doing right now. An energy audit shows what that equipment costs you, what it should do instead, and which sensor readings you should not trust.

The BAS Only Knows What it can Measure

A BAS is built to report the points that someone wired and mapped to it. A point is a single reading, such as a temperature or a fan status. This is extremely helpful for facility operators who are spread thin and need to know the status of their units at a glance. The amount of data a BAS can pull together is truly amazing and incredibly useful.
A BAS does not know how the building should run unless that is written in the sequence of operations. Operators are able to set parameters for equipment such as temperature, but even then, it cannot tell you whether the sequence is truly beneficial for your building. A typical BAS also does not read your utility bills unless it is able to receive that information and process it correctly.
In short, a BAS can show every air handling unit (AHU) running, every room near its temperature setpoint and no alarms. This is usually a perfect scenario and on paper, can look like your building is running at an optimal level. Unfortunately for owners, the building can still be wasting energy that their BAS is not built to flag.

Sensors that are Wrong but look Right

A standard BAS treats every sensor value as true, so a wrong sensor usually raises no alarm. A drifted outdoor air temperature sensor can read several degrees warm. The economizer that controls that uses outdoor air for free cooling, stays locked out on mild days. A wrong mixed air sensor can blend the return and outdoor air incorrectly. making the air damper fight the cooling coil.
An energy audit checks key sensors against a calibrated reference in the field. It also compares related readings with each other. Because mixed air is a blend, its temperature should fall between the tolerance of return air and outdoor air temperatures. If it does not, we check the sensors and make sure their readings are correct individually as well as if they are communicating between each other.

Equipment the BAS Doesn't See

Many buildings have equipment and sensors that are not on the BAS. Examples are stand-alone thermostats, exhaust fans on local switches, packaged units with their own controls, lighting, and process loads. One of our employees conducting an energy audit walks the building and lists every major energy user, including the ones with no data point in the BAS. Control Service Company compares that list with the BAS point list and checks any equipment set to manual override, which can look like normal operation on a graphic.

The Money Side

Your BAS reports temperatures, positions and status. The utility bills report dollars. An audit puts them side by side and helps us make a plan for your building.
The audit reads the rate, the read type (actual or estimated), the usage and the peak demand on every bill. Peak demand is your highest power use in a short period, often captured in a 15-minute interval. The audit compares these figures with trend data (the logged history of BAS readings) for the same period.
When we compare this data, it shows when a peak demand charge came from every AHU starting at the same minute. It also shows when a rate change raised the cost of a load that had not changed. A typical BAS does not show the dollar effect of either one, but a good energy audit can reveal what both can’t capture on their own.

How BAS Data and Audits Fit Together

Trend data from your BAS is one of the best comparison tools you have when conducting an audit. It shows how the equipment has run over weeks and seasons. The audit adds three things to your tool kit.
1) It checks that the data is correct.
2) It adds the costs from the utility bills.
3) It ranks what to fix.

ASHRAE (the American Society of Heating, Refrigerating and Air-Conditioning Engineers) describes energy audits in three levels.

A Level 1 audit is a walk-through with a bill review.
A Level 2 audit adds a detailed survey and an engineering analysis of energy conservation measures (changes that save energy).
A Level 3 audit adds a detailed cost study of large projects that need new equipment.

A building with a working BAS gains the most savings from a Level 2 audit, because the BAS makes trend data easy to collect. After reviewing data and adjusting setpoints, a level 3 may become necessary and will uncover physical equipment inefficiencies.

What an Audit does NOT do

An audit is a snapshot. It does not watch the building every day, and the problems it finds can return. Settings drift and overrides come back. The audit finds the waste, but someone must then fix it and keep it fixed. This can sometimes be handled by a facility manager, but an outside eye is recommended.
Where to start
• Collect twelve months of utility bills for each meter.
• Note any recent change in how the building is used, such as new hours, new rooms or new equipment.
• Keep track of and list the comfort complaints of the last year and the rooms they came from.

Why an Outside Auditor finds More

Your financial staff can gather the bills. You know the building hours and normal use time. A facility manager can read the BAS and see trend data and setpoints. The next step is to compare them. The harder part is knowing what to do with all the data and detailing the next steps.
A person who has audited many buildings knows what a normal mixed air reading looks like. That person also knows what the sequence of operations is, what it should do, and how each rate on a bill compares to the physical infrastructure. Your staff runs the building every day, and they have their hands full with the day-to-day operations. They rarely have time to build the necessary skills to be an energy manager or to repeat the comparison and audit on a normal basis.
An energy manager is a trained person who reviews BAS data and utility bills each month or at consistent intervals. They compare data from month to month, and year to year, and can recognize gaps and inefficiencies that don’t show up in the day-to-day readings of your BAS. Savings are then estimated against a baseline: past usage from the bills, adjusted for weather so a hot month is not read as waste.
Energy managers go a step beyond what a BAS can do and what onsite staff have time for. They are trained for the long-term energy savings and are there to do what’s best for your building and for your bottom line.

CSC's Energy Managers & Services

You can continue to try to manage energy expenditure on your own. Or you could contact Control Service Company! Send us the last twelve months of utility bills. If you are one of our BAS clients, we can compare it to your system from our office, so the review is a desk study and not an on-site audit. The review lists where the BAS data and the bills disagree. It gives an estimated yearly cost for each gap and states whether a Level 2 audit is worth doing.
Call 816.600.5800 or fill out our Contact Us form to confirm the scope and if you qualify for a free level 1 review.