Most buildings that waste energy look fine. The rooms are comfortable, the alarms are quiet and the building automation system (BAS) shows green across the board. The waste hides in settings that have drifted away from how the building should run. And unfortunately, it shows up every month on the utility bill.

7 Hidden Problems Causing your Building to Waste Energy
An energy audit reads the building two ways. It reads what the BAS is doing, from trend data (the logged history of BAS readings within the dashboard). It also reads what the building pays for, using utility bill data. When the two disagree, you’re the one left paying for the difference. Here are seven common problems to look for when your bulls are getting higher.
1. Outdoor Air When Nobody’s There
Air handling units (AHUs) are the central units that move air through the building. They bring in outdoor air to ventilate occupied spaces. At night, on weekends and over breaks, that ventilation is not needed. Many AHUs serve variable air volume (VAV) boxes. A VAV box is the terminal unit that controls the air to one zone, the area it serves.
An AHU that serves VAV boxes runs on zone requests, which are calls from the rooms for heating or cooling. When a zone misses its setpoint (the target temperature), its box sends a request to the AHU. Wrong zone schedules, or unoccupied setpoints set too tight, can keep the AHU running at night. If the outdoor air damper also fails to close, the AHU heats or cools outdoor air for an empty building.
The fix is often a change in the existing BAS. The change is to the zone schedules or to the sequence of operations.
What to check: Walk the building at night or on a weekend and note what is running while the rooms are empty. Note the names or locations of those units. A night run is not always a waste. Early warm-up, night temperature setback (a wider night setpoint) and freeze protection can start a unit. In our review, Control Service Company traces each night run to the zone requests that started it. It also checks whether the outdoor air damper is closed.
2. Heating and Cooling at the Same Time
In a VAV reheat system, the AHU cools the air it supplies, and each VAV box reheats that air as needed. Some reheat is normal. Too much can get expensive. The usual causes are a minimum airflow setpoint above what the space needs, and a setpoint too low for the air the AHU supplies to the space.
Newer sequences of operation limit this waste. ASHRAE 36 is one example. It is a published set of standard sequences from the American Society of Heating, Refrigerating and Air-Conditioning Engineers. The standard sets how cool the air leaving the AHU should be. This rule is a reset: the target rises or falls with what the rooms need. It also sets the minimum airflow of each box from ventilation needs.
What to check: On a mild day when the building is being cooled, feel the air at the vents in several rooms. Many vents blowing warm air may cause a reheat, a leaking valve, or that air from the AHU is too cold. Treat this as a question, not a diagnosis. In our review, Control Service Company counts the reheating boxes from your BAS data, checks the minimum airflow, and the supply air temperature reset.
3. Schedules that Drifted
A schedule should tell equipment when the building is occupied. Someone might change it for a meeting, a ball game or a cleaning crew, and nobody changes it back. Holidays never get loaded in. Educational institutions keep the full school-year schedule all summer. Each change presented is small, but together they can add up to many “occupied” hours a year. Zones in “occupied” mode send more requests to the AHU and to the heating and cooling plants, driving up your bills.
What to check: Write down the hours your building really runs and its holiday schedule, including summer. In our review, Control Service Company compares the zone schedules and the schedules of any stand-alone equipment in your BAS, with that calendar line by line. When the schedules don’t match up, we purpose adjustments and automations that better suit the actual necessary usage hours.
4. Overrides Left in Place
A technician sets a fan, a valve or a setpoint to a manual override to fix an individual hot or cold complaint. It works, the complaint is closed, but the override stays for months. An override can hide an underlying issue like a stuck damper or valve. The BAS shows that the equipment is running, so nobody notices that it is no longer operating under automatic control.
What to check: Note which rooms have had hot or cold complaints this year. Overrides often start there. In our review, Control Service Company pulls the override report from the BAS and lists every fan, valve and setpoint set to manual. Every override should have a reason and an end date.
5. Setpoints that Creep
A hot or cold complaint from a tenant often ends with a setpoint moved one or two degrees. A year later, the thermostat has been adjusted, and room temperatures may sit several degrees outside your building’s setpoint standard. An example of a standard is 70°F for heating and 74°F for cooling when occupied. Each degree of drift can cost energy all day, every day.
What to check: Write down your building’s setpoint standard. If none exists, write down what the wall thermostats show in several rooms. List the rooms that draw complaints and figure out what your standard schedule should be. In our review, Control Service Company helps you create a standard then compares every zone with it. We then correct the setpoints that have drifted and address the cause of the complaints in an individual basis.
6. Peak Demand
Many commercial electric utility providers base your bill off your highest power use in any short period, often as little as 15 minutes. This is “peak demand”. It can determine a large part of the facility’s monthly bill. It often comes from equipment that starts up at the same time in the morning, or from regular daytime temperatures that the BAS does not account for. Anytime a large percentage of your equipment is running at once.
Many BAS platforms include demand limiting, which holds back equipment when power use nears a set peak. This is not a feature that is regularly utilized. It can lower peak demand, but the result depends on the rate and the load of equipment. Some rates carry a ratchet (a clause that holds a past peak on the bill for months), so the savings can arrive late. The tuning must keep the rooms comfortable for the inhabitants.
What to check: If your bill shows when the peak happened, note the day and time. A peak near morning start-up points to equipment that starts all at once. In our review, Control Service Company checks the start times of large equipment and adjusts the start time where needed. WebCTRL offers temperature settings so we can track any seasonal adjustments needed as well.
7. Bill Errors Nobody Checks
Utility bills can carry wrong rates, estimated reads, meters billed to the wrong account and rate changes that nobody announced. These are real dollars, and they repeat every month until someone finds them. Few people read utility bills line by line unless it is their job.
What to check: Find the rate name, whether the read is actual or estimated, and the kWh on each bill. Compare each with the same month last year. A sudden change in usage with no change in the building is a question for the utility.
Why these problems hide
A typical BAS shows what the building is doing, not what it should be doing. Most of these problems look normal on a standard BAS graphic, and bill errors usually do not appear on a BAS at all.
Where to start
· Collect the last twelve months of utility bills for each meter.
· Walk the building at night and on a weekend, and note what runs.
· Write down the hours your building really runs, the holidays and your building’s setpoint standard.
Doing it yourself vs. calling an energy manager
You can always spend the time and manpower to follow the steps above, and many owners should start there before moving onto an energy manager. The next step would be hiring an energy manager, they’re a specialist who will read BAS data against utility bills every month.
Time and skill
Checking every air handler and VAV box for these problems takes days. Most facility staff do not have that time between the other numerous jobs they have during the day. Leave it to Energy Managers who know exactly what to look for and how they correlate to your bills.
What a typical BAS does not tell you
A typical BAS shows what the building is doing, not what it should do. To find the gap, a person must know the sequences of operation, the setpoint standards and the rate structures of the utilities. Energy Managers have the training and their whole job is to save your building money.
Keeping the fix
Fixing is the easy part. Settings drift back and overrides return. An Energy Manager compares trend data with the utility bills every month Drift shows up early and an Energy Manager knows how to check back and keep those setpoints in line.
Savings on the Bills
An energy manager estimates savings against a baseline: the past usage of the building from the bills, adjusted for weather. The owner can then compare the estimate with the bills.
Control Service Company needs only the utility bills for the last twelve months of each meter. We pull the trend data, zone schedules and override reports from the BAS itself. The review states which of these seven problems your building shows and gives an estimated yearly cost for each. Ask about the scope and fee on 816.600.5800 or fill out our contact us form.
Contact Control Service Company to get started.